SCOPE OF ACCREDITATION   View and Print Scope of Accreditation Printable version

Note: Not all of the columns of the scope of accreditation displayed include data.
The only data displayed is that deemed relevant and necessary for the clear description of the activities and services covered by the scope of accreditation.
Grey text appearing in a SoA is additional freetext providing further refinement or information on the data in the preceding line entry.



ISO/IEC 17025 (2017)
Calibration
SERVICEPRODUCTDETERMINANTTECHNIQUEPROCEDURELIMITATION / RANGE
DC and low frequency electrical metrology - Electrical measurement and test equipment
Insulation resistance test equipment;
Resistance;
Comparison with a reference standard by substitution measurement;
By the method of PSS WI-11 At voltages of 50 V to 5 kV
CAPABILITY
with Calibration and Measurement Capability of;
3% from 1 MΩ - 1 GΩ;
5% from 1 GΩ - 10 GΩ;                    
10% from 10 GΩ - 100 GΩ;

Ammeters;
AC current;
Indirect measurement against a reference standard;
by method of single or multiple turns from 50 mA up to 5000 A at 50 Hz 
CAPABILITY
with Calibration and Measurement Capability of -;
1% of reading;
from 50 mA up to 5000 A at 50 Hz;
DC and low frequency electrical metrology - High-voltage/high-current standards and equipment
Current transformers;
Current error; Phase displacement;
Comparison with a reference standard by differential measurement;
AS 1675;
AS/IEC 60044.1;
IEC 61869-1,-2
CAPABILITY
Accuracy tests at 50 Hz, up to 5000 A applied primary current;
for CTs with rated secondaries of 1 A or 5 A;
with Calibration and Measurement Capability of -;
±0.025% for current error;
±0.030 crad for phase displacement;

Voltage transformers;
Phase displacement; Voltage error;
Comparison with a reference standard by differential measurement;
AS 1243;
AS/IEC 60044.2
AS/IEC 61869-1,-3;
CAPABILITY
Accuracy tests at 50 Hz, up to rated primary voltage of 132 kV/√3;
Single phase measurements of VTs with rated secondaries of 63.5 V or 110 V;with Calibration and Measurement Capability of -;
0.025% for voltage error;
0.025 crad for phase displacement;

High voltage test sets;
Voltage;
Direct measurement against a reference standard;

Measurements performed in the laboratory and in the field ;
a.c. test sets
from 1 kVrms to 100 kVrms at 50 Hz;
from ±1 kVpeak/√2 to ±100 kVpeak/√2, at 50 Hz;

from ±1 kVpeak to ±140 kVpeak, at 50 Hz;

d.c. test sets
from - 90 kV to +90 kV

CAPABILITY
Measurements performed in the laboratory;
with Calibration and Measurement Capability of -;  

a.c. test sets

2% of reading from 1 kVrms to 100 kVrms at 50 Hz;
2% of reading from ±1 kVpeak/√2 to ±100 kVpeak/√2, at 50 Hz;

2% of reading from ±1 kVpeak to ±140 kVpeak, at 50 Hz;

d.c. test sets
2% of reading from -90 kV to 90 kV

Measurements performed in the field;

with Calibration and Measurement Capability of;

a.c. test sets
2.5% of reading from 1 kVrms to 100 kVrms at 50 Hz;
2.5% of reading from ±1 kVpeak/√2 to ±100 kVpeak/√2, at 50 Hz;
2.5% of reading from ±1 kVpeak to ±140 kVpeak, at 50 Hz;

d.c. test sets
2.5% of reading from -90 kV to 90 kV


ISO/IEC 17025 (2017)
Infrastructure and Asset Integrity
SERVICEPRODUCTDETERMINANTTECHNIQUEPROCEDURELIMITATION / RANGE
Evaluation of high voltage/power equipment and components - Performance
Clothing materials, gloves and tools for use in high voltage/power applications;
AC voltage; Applied high voltage withstand; Electrical performance of cables and components; Workplace electrical safety;
High voltage; Surface leakage;
 ISSC14 Guide to electrical workers' safety equipment chapter 13;
 PSS WI-12
At 50 Hz up to 45 kV
       

High voltage operating sticks



Transformers and inductors;
Accuracy tests;
Phase displacement; Voltage error;
IEC and AS 60044.2;
AS1243:1982 Superseded;
IEC 61869-1; and IEC 61869-3; Instrument transformers - Voltage transformers
Accuracy tests at 50 Hz up to rated primary voltage of 132 kV/√3;
Single phase measurements of voltage transformers with rated secondaries of 63.5 V or 110 V 


Accuracy tests;
Current error; Phase displacement;
IEC and AS 60044.1: Instrument Transformers-Current Transformers;
IEC 61869-1 and IEC 61869-1 -2: Instrument Transformers-Current Transformers;
AS 1675: 1986 Withdrawn Instrument Transformers-Measurement & Protection
Accuracy tests at 50 Hz up to 5000 A applied primary current
for current transformers with rated secondaries of 1 A or 5 A

Bushings; Cable feeders; Cables; Clothing materials, gloves and tools for use in high voltage/power applications; Insulated systems; Insulation products; Insulator and conductor fittings; Insulators; Three phase cable installations; Transformers and inductors;
Insulation resistance;
Insulation resistance;
By the method of PSS WI-10
Tests performed in the laboratory and in the field;
From 1 MΩ to 100 GΩ at voltages of 50 Vdc to 5,000 Vdc